| Tabel 1 | Unit | ZW32-12/630-20 | ZW32-12/630-25 | |
| Tegangan sing dirating | kV | 12 | ||
| Arus sing dirating | A | 630 1250 | ||
| Arus pemutus sirkuit cendhak sing dirating | kA | 20 | 25 | |
| Arus penutupan sirkuit cendhak sing dirating (puncak) | 50 | 63 | ||
| Arus tahan puncak sing dirating | 50 | 63 | ||
| Arus tahan wektu cendhak sing dirating | 20 | 25 | ||
| Wektu terus-terusan sirkuit cendhak sing dirating | s | 4 | ||
| Tingkat insulasi sing dirating | Tegangan tahan impuls petir (puncak) | kV | Interfase, menyang lemah 75, fraktur 85 | |
| Tegangan tahan frekuensi daya 1 menit | Interfase, menyang lemah 42, fraktur 48 | |||
| Urutan operasi sing dirating | O-0.3s-CO-180s-CO (Operasi listrik) | |||
| Wektu pemutus arus hubung singkat sing dirating | Siklus | 30 | ||
| Urip listrik | 10000 | |||
| Tegangan operasi sing dirating (Koil pambuka lan panutup) | V | DC220, 110, AC220 | ||
| Ngobahake lan ndandani kontak sing diidinake kekandelan akumulasi | mm | 3 | ||
| Arus sing dirating saka tripping arus sing luwih gedhe | A | 5 | ||
| Rasio arus transformator arus (reguler) | 200/5 400/5 630/5 | |||
| Jarak bukaan kontak | mm | 9±1 | ||
| Kontak overstroke | 2⁺¹₋₀.₅ | |||
| Kacepetan pambukaan rata-rata | m/s | 1.2±0.2 | ||
| Kacepetan nutup rata-rata | 0.6±0.2 | |||
| Wektu buka | ms | 15~50 | ||
| Wektu nutup | 25~80 | |||
| Wektu nutup tripping | ≤2 | |||
| Sinkronisasi pambuka lan panutup telung fase | ≤2 | |||
| Resistansi DC saben sirkuit fase | mΩ | ≤80 | ||
| Motor panyimpenan energi | Tegangan sing dirating | V | DC/AC 220 | |
| Daya sing dirating | W | 70 | ||
| Wektu panyimpenan energi | S | ≤8 | ||
| Bobot | kg | 100 | ||
Diagram 1 ZW32-12 Pemutus sirkuit vakum tegangan tinggi njaba ruangan
Diagram 2 ZW32-12(G) Pemutus sirkuit vakum tegangan tinggi njaba ruangan
Diagram 3 ZW32-12(G) Dimensi instalasi pemutus sirkuit vakum tegangan tinggi njaba ruangan