| RDW8 | HU | 25 | 16 | 3 | H | Tingkat laci | AC230V | Ora ana undervoltage |
| Kode produk | Nilai sing ora apik | Arus pigura | Arus sing dirating | Cacahing tiang | Kontroler | Mode instalasi | Tegangan kontrol | Lampiran |
| Tegangan dhuwur cerdas Pemutus sirkuit universal | HU | 25:2500(06-25) 40:4000(08-40) 63:6300(40-63) | 06:630A 08:800A 10:1000A 12:1250A 16:1600A 20:2000A 25:2500A 29:2900A 32:3200A 36:3600A 40:4000A 50:5000A 60:6000A | 3:3P 4:4P | M: Tipe standar (Tampilan digital) R: Jinis sing luwih apik (Layar kristal cair) H: Tipe canggih (LCD nganggo komunikasi) | Tingkat laci Laci vertikal Tingkat tetep Vertikal tetep | AC230V AC400V DC220V DC110V | Partisi antarfase Transformasi papat kali lipat Kusen lawang Ora ana undervoltage Tegangan ngisor sesaat Ing wektu kalender Interlocking mekanik Interlocking mekanik Siji gembok, siji kunci Loro kunci lan siji kunci Telung kunci, loro kunci Iku 50-50 Enem ing, enem off |
● Konfigurasi standar standar RDW8HU: shunt, penutupan, operasi listrik, konversi 4 grup, kusen lawang, partisi interfase
● Contone: kudu pesen RDW8HU-2500, laci telung kutub, arus terukur 1250A, pengontrol cerdas kanggo tipe R, voltase kontrol AC230V
● Ditulis minangka: RDW8HU-25 12/3R tingkat laci AC230V tanpa voltase kurang.
Kondisi kerja normal
■ Suhu udara sekitar yaiku -5℃ ~ +40℃, lan nilai rata-rata 24 jam ora ngluwihi +35°C;
Cathetan:Yen wates ndhuwur ngluwihi +40℃ utawa wates ngisor luwih murah tinimbang -5℃, pangguna kudu rembugan karo pabrikan.
■ Elevasi lokasi instalasi ora ngluwihi 2000m;
Cathetan:Konsultasi karo pabrike babagan pemutus sirkuit sing digunakake ing lingkungan kerja kanthi ketinggian luwih saka 2000m.
■ Kelembapan relatif atmosfer ora ngluwihi 50% nalika suhu udara sekitar +40℃; Kelembapan relatif bisa luwih dhuwur ing suhu sing luwih endhek. Contone, sasi paling teles duwe kelembapan relatif maksimum rata-rata 90%, dene suhu minimum rata-rata sasi yaiku +20℃, lan langkah-langkah perawatan kudu ditindakake kanggo kondensasi sing sok-sok kedadeyan amarga owah-owahan suhu.
■ Tingkat polusi yaiku 3;
■ Nalika voltase kerja sing dirating ing sirkuit utama yaiku AC 800V ~ AC1140V, sirkuit kontrol lan sirkuit bantu kudu diisolasi saka sirkuit utama dening transformator, lan voltase kerja maksimum saka sirkuit kontrol lan sirkuit bantu yaiku AC400V, kategori instalasi sirkuit kontrol lan sirkuit bantu yaiku Ⅲ;
■Pemutus sirkuit iki cocok kanggo lingkungan elektromagnetik A;
■Gunakake kategori B.
Kondisi instalasi normal
■ Pemasangan pemutus sirkuit tetep: Pemutus sirkuit diselehake ing kabinet distribusi lan diamanake nganggo baut lan ring M10 (luwih saka 2500A).
Pemutus sirkuit dipasang kanthi lancar tanpa tekanan mekanik tambahan.Hindari kerusakan pemutus sirkuit utawa kontak busbar utama sing ora apik;
■ Pemasangan pemutus sirkuit tipe laci: Copot awak pemutus sirkuit saka kursi laci, pasang kursi laci ing distribusikabinet dhisik,lan kencengna nganggo baut lan ring M10 (luwih saka 2500A). Tingkat pemasangan pemutus sirkuit stabil, ora kena ana tekanan mekanik tambahan, supaya ora ana kerusakan pemutus sirkuit utawa kontak sing ora apik antarane bus utama lansirkuit sekunder,sawise rampung awak pemutus sirkuit menyang posisi sambungan kursi laci;
■Pemutus sirkuit kudu dipasang ing panggonan sing ora ana risiko bledosan lan bledug konduktif, tanpa cukup kanggo ngrusak logam lanngrusak insulasi;
■Tingkat proteksine yaiku IP20, Nalika pemutus sirkuit dipasang ing kabinet lan kusen lawang dipasang, tingkat proteksine bisatekan IP40.
Kahanan panyimpenan lan transportasi normal
■ Wates suhu ngisor ora kurang saka -25℃, wates ndhuwur ora luwih saka +55℃; Kelembapan relatif (+25℃) ora ngluwihi95%;
■Produk kudu ditangani kanthi alon-alon sajrone transportasi, lan aja diwalik supaya ora tabrakan kanthi kasar.
| Cacahing kutub (Tabel 1) | 3P/4P | ||||||||
| Frekuensi | 50/60Hz | ||||||||
| Tegangan operasi sing dirating Ue(V) | AC800V/AC1000V/AC1140V | ||||||||
| Tegangan tahan impuls sing dirating Uimp (kV) | AC12kV | ||||||||
| Tegangan insulasi sing dirating Ui(V) | AC1250V | ||||||||
| Kelas pigura | 25HU | 40HU | 63HU | ||||||
| Ing (A) | |||||||||
| 630 | ● | ||||||||
| 800 | ● | ● | |||||||
| 1000 | ● | ● | |||||||
| 1250 | ● | ● | |||||||
| 1600 | ● | ● | |||||||
| taun 2000 | ● | ● | |||||||
| 2500 | ● | ● | |||||||
| 2900 | ● | ||||||||
| 3200 | ● | ||||||||
| 3600 | ● | ||||||||
| 4000 | ● | ● | |||||||
| 5000 | ● | ||||||||
| 6300 | ● | ||||||||
| Kapasitas pemecahan (AC800V) | AC800V | AC1000V | AC1140V | AC800V | AC1000V | AC1140V | AC800V | AC1000V | AC1140V |
| Kapasitas pemutus sirkuit cendhak watesan sing dirating Icu(KA) | 60 | 55 | 50 | 75 | 60 | 60 | 85 | 66 | 66 |
| Kapasitas pemutus sirkuit pendek operasi sing dirating Ics (KA) | 60 | 55 | 50 | 75 | 60 | 60 | 85 | 66 | 66 |
| Daya tahan jangka pendek sing dirating Icw/1s(KA) | 60 | 55 | 50 | 75 | 60 | 60 | 85 | 66 | 66 |
| Wektu segmen lengkap (ora ana wektu tundha tambahan) | 25~30ms | ||||||||
| Wektu nutup | ≤70ms | ||||||||
| Umur mekanik (karo perawatan) | 20000 | 20000 | 13000 | ||||||
| Umur mekanik (tanpa perawatan) | 10000 | 10000 | 6500 | ||||||
| Urip listrik | 7000 | 6000 | 1500 | ||||||
| Mode sambungan (horizontal) | ● | ||||||||
| Mode sambungan (vertikal) | ● | ||||||||
| Mode sambungan (horizontal ndhuwur lan vertikal ngisor) Mode sambungan (vertikal munggah lan horisontal mudhun) | ● | ||||||||
Cathetan:Umur mekanik kursi laci yaiku 100 kali, saka "pemisahan" nganti "sambungan" nganti "pemisahan" mung sapisan, lan siklus operasi yaiku 1 kali /2 menit.
①Model pengontrol cerdas(model produk sing cocog);
②Jendhela tampilan kristal cair LCD: bisa nampilake saben nilai arus fase, nilai voltase, parameter setelan, arus gangguan, aliran, wektu trip lan parameter pitakon informasi;
③Pratandha kesalahan wektu tundha dawa sing berlebihan;
④Pratandha wektu tundha cendhak sirkuit cendhak;
⑤Pratandha gangguan lemah utawa netral;
⑥Tombol setelan:Cepet ngalih menyang menu utama setelan parameter, (ing antarmuka input sandhi ana tombol "Tengen");
⑦Kunci pangukuran: Cepet ngalih menyang menu utama standar pangukuran, (ing antarmuka input sandhi ana tombol "Kiri");
⑧Tombol Munggah:Pindhah isi menu munggah ing level saiki, utawa ganti pilihan munggah Parameter;
⑨Tombol Mudhun:Pindhah isi menu mudhun ing level saiki, utawa ganti pilihan mudhun Parameter;
⑩Tombol mburi:Metu saka level saiki kanggo mlebu menu level ndhuwur, utawa batalake parameter saiki sing dipilih;
⑪Tombol Ok:Ketik menu level sabanjure sing dituduhake item saiki, utawa terusake menyang parameter saiki Pilih, simpen pangowahan sing digawe;
⑫Tombol pitakon:Ngalih menyang menu tema riwayat lan pangopènan;
⑬Tombol setelan parameter proteksi:Ngalih menyang menu tema setelan parameter pangayoman;
⑭Indikasi gangguan sirkuit cendhak sesaat;
Indikasi kesalahan wektu tetep wektu tundha cendhak sirkuit cendhak;
⑯Indikasi komunikasi:
Profibus: ora ana komunikasi nalika mati, komunikasi tetep padhang;
Modbus: mati nalika ora ana komunikasi sing kasedhiya lan kedhip nalika komunikasi kasedhiya.
⑰Indikasi normal:ing kahanan daya, kahanan kerja normal, LED tansah ijo kedhip-kedhip;
⑱Indikasi kesalahan/alarmLED "kesalahan/alarm" ora murub nalika operasi normal; rusak nalika trip, LED "Kesalahan/alarm" abang lan kedhip-kedhip kanthi cepet; Yen ana alarm nalika LED abang tetep padhang;
⑲Tombol ResetNalika kontroler cerdas ana ing kahanan kesalahan/alarm, kudu mulihake menyang kahanan kerja normal, pencet tombol iki kanggo mbusak indikasi kesalahan/alarm kontroler cerdas.
| Nilai set arus aksi Ir (Tabel 2) | (0.4~1.0)Mlebu+MATI | Toleransi saiki | ±10% | ||||||||||||||
| Arus sing ditrapake I | Nyetel wektu lelungan | ||||||||||||||||
| 1.05Ir | >2 jam ora trip | ||||||||||||||||
| 1.3Ir | < 1 jam Lelungan | ||||||||||||||||
| Tipe karakteristik pangayoman | Arus gangguan | Nyetel wektu Tr (s) | |||||||||||||||
| Wektu kebalikan standar SI | 1.5Ir | 0.61 | 0.98 | 1.47 | 2.46 | 3.68 | 4.91 | 6.14 | 9.21 | 11.05 | 17.19 | 24.56 | 36.84 | 49.13 | 61.41 | 73.69 | 85.97 |
| 2Ir | 0.36 | 0.57 | 0.86 | 1.43 | 2.15 | 2.87 | 3.58 | 5.37 | 6.45 | 10.03 | 14.33 | 21.49 | 28.65 | 35.82 | 42.98 | 50.15 | |
| 6Ir | 0.14 | 0.22 | 0.33 | 0.55 | 0.82 | 1.1 | 1.37 | 2.06 | 2.47 | 3.84 | 5.48 | 8.22 | 10.96 | 13.7 | 16.45 | 19.19 | |
| 7.2Ir | 0.12 | 0.2 | 0.3 | 0.5 | 0.74 | 0.99 | 1.24 | 1.86 | 2.23 | 3.48 | 4.97 | 7.45 | 9.93 | 12.42 | 14.9 | 17.38 | |
| Kacepetan VI wektu kosok baline | 1.5Ir | 2 | 3.2 | 4.8 | 8 | 12 | 16 | 20 | 27 | 36.6 | 56 | 80 | 120 | 160 | 200 | 240 | 280 |
| 2Ir | 1 | 1.6 | 2.4 | 4 | 6 | 8 | 10 | 13.5 | 18 | 28 | 40 | 60 | 80 | 100 | 120 | 140 | |
| 6Ir | 0.2 | 0.32 | 0.48 | 0.8 | 1.2 | 1.6 | 2 | 2.7 | 3.6 | 5.6 | 8 | 12 | 16 | 20 | 24 | 28 | |
| 7.2Ir | 0.16 | 0.26 | 0.39 | 0.65 | 0.97 | 1.29 | 1.61 | 2.18 | 2.9 | 4.52 | 6.45 | 9.68 | 12.9 | 16.13 | 19.35 | 22.58 | |
| Wektu terbalik EI(G)Ekspres (Perlindungan distribusi umum) | 1.5Ir | 8 | 12.8 | 19.2 | 32 | 48 | 64 | 80 | 108 | 144 | 224 | 320 | 480 | 640 | 800 | 960 | 1000 |
| 2Ir | 3.33 | 5.33 | 8 | 13.33 | 20 | 26.67 | 33.33 | 45 | 60 | 93.33 | 133.33 | 200 | 266.67 | 333.33 | 400 | 433.33 | |
| 6Ir | 0.29 | 0.46 | 0.69 | 1.14 | 1.71 | 2.29 | 2.86 | 3.86 | 5.14 | 8 | 11.43 | 17.14 | 22.86 | 28.57 | 34.29 | 37.14 | |
| 7.2Ir | 0.2 | 0.31 | 0.47 | 0.79 | 1.18 | 1.57 | 1.97 | 2.66 | 3.58 | 5.51 | 7.87 | 11.8 | 15.74 | 19.67 | 23.6 | 25.57 | |
| Wektu terbalik EI(M) Ekspres (Proteksi motor) | 1.5Ir | 6.22 | 9.96 | 14.93 | 24.89 | 37.34 | 49.78 | 62.23 | 84.01 | 112.01 | 174.24 | 248.91 | 373.37 | 497.82 | 622.28 | 746.73 | 208.96 |
| 2Ir | 2.95 | 4.72 | 7.07 | 11.79 | 17.69 | 23.58 | 29.48 | 39.79 | 53.06 | 82.53 | 117.9 | 176.86 | 235.81 | 294.76 | 353.71 | 383.19 | |
| 6Ir | 0.28 | 0.45 | 0.68 | 1.13 | 1.69 | 2.26 | 2.82 | 3.81 | 5.08 | 7.9 | 11.29 | 16.94 | 22.58 | 28.23 | 33.88 | 36.7 | |
| 7.2Ir | 0.2 | 0.31 | 0.47 | 0.78 | 1.17 | 1.56 | 1.95 | 2.63 | 3.51 | 5.46 | 7.8 | 11.7 | 15.61 | 19.51 | 23.41 | 25.56 | |
| Sekring voltase dhuwur sing kompatibel karo HV | 1.5Ir | 2.46 | 3.94 | 5.91 | 9.85 | 14.77 | 19.69 | 24.62 | 33.23 | 44.31 | 68.92 | 98.46 | 147.69 | 196.92 | 246.15 | 295.38 | 320 |
| 2Ir | 0.67 | 1.07 | 1.6 | 2.67 | 4 | 5.33 | 6.67 | 9 | 12 | 18.67 | 26.67 | 40 | 53.33 | 66.67 | 80 | 86.67 | |
| 6Ir | 0.01 | 0.01 | 0.02 | 0.03 | 0.05 | 0.06 | 0.08 | 0.1 | 0.14 | 0.22 | 0.31 | 0.46 | 0.62 | 0.77 | 0.93 | 1 | |
| 7.2Ir | 0 | 0.01 | 0.01 | 0.01 | 0.02 | 0.03 | 0.04 | 0.05 | 0.07 | 0.1 | 0.15 | 0.22 | 0.3 | 0.37 | 0.45 | 0.48 | |
| Proteksi wektu terbalik universal I²T | 1.5Ir | 15 | 30 | 60 | 120 | 240 | 360 | 480 | 600 | 720 | 840 | 960 | |||||
| 2Ir | 8.44 | 16.88 | 33.75 | 67.5 | 135 | 202.5 | 270 | 337.5 | 405 | 472.5 | 540 | ||||||
| 6Ir | 0.94 | 1.88 | 3.75 | 7.5 | 15 | 22.5 | 30 | 37.5 | 45 | 52.5 | 60 | ||||||
| 7.2Ir | 0.65 | 1.3 | 2.6 | 5.21 | 10.42 | 15.63 | 20.83 | 26.04 | 31.25 | 36.46 | 41.67 | ||||||
Cathetan:AkuFitur proteksi wektu tundha dawa pengontrol cerdas standar pabrik yaiku I²T proteksi wektu kebalikan universal: I2TL=(1.5Ir) 2t, tL-wektu tundha dawa wektu setelan 1.5Ir, TL-wektu aksi wektu tundha dawa, kesalahan wektu operasi ±15%.
Diagram kabel sirkuit sekunder tipe-R RDW8HU-2500/4000/6300 Fungsi terminal lan interpretasi simbol
| Nomer terminal | Katrangan Fungsi | Simbol | Parafrase | Cathetan |
| 1, 2 | Input daya tambahan: AC230V, AC400V, DC220V, DC110V | RDW8HU | Pemutus sirkuit universal RDW8HU | |
| 3, 4, 5 | Kontak bantu trip gangguan, kapasitas kontak: AC250V, 3A | S1~S4 | Lampu sinyal | Pangguna sing diwenehake |
| 20 | Tanah (PE) | TA | Transformator arus | |
| 21, 22, 23, 24 | Pangukuran sinyal voltase, 21 disambungake menyang fase N, 22 disambungake menyang fase A, 23 disambungake menyang fase B, 24 disambungake menyang fase C | SAL | saklar mikro | |
| 27, 28 | Pelepasan undervoltage | SB1 | Tombol pambuka | Pangguna sing diwenehake |
| 29.30 | Pelepasan shunt | SB2 | Tombol nutup | Pangguna sing diwenehake |
| 31, 32 | Elektromagnet sing nutup | X | Elektromagnet sing nutup | |
| 33, 34, 35 | Mekanisme operasi listrik (panyimpenan energi listrik), 37 disambungake karo garis ijo, 38 disambungake karo garis ireng, 39 disambungake karo garis abang | F | Pelepasan shunt | |
| 36~48 | Terminal kontak bantu | Q | Pelepasan undervoltage | |
| ★Amarga voltase sirkuit utama seri iki yaiku voltase dhuwur, pangukuran sinyal voltase saka kontroler tipe R/H 21,22/23,24 kudu disambungake menyang modul konversi voltase. | M | Mekanisme operasi listrik | ||
| SA | Saklar travel mekanisme operasi listrik | |||
| Fu | sekering | Pangguna sing diwenehake | ||
| PE | Kabel lemah | |||
| N | Netral (fase N) | |||
| A, B, C | Garis fase | |||
| AX | Kontak bantu | |||
Diagram kabel sirkuit sekunder tipe-H RDW8HU-2500/4000/6300 Fungsi terminal lan interpretasi simbol
| Nomer terminal | Katrangan Fungsi | Simbol | Parafrase | Cathetan |
| 1, 2 | Input daya tambahan: AC230V, AC400V, DC220V, DC110V | RDW8HU | Pemutus sirkuit universal RDW8HU | |
| 3, 4, 5 | Kontak bantu trip gangguan, kapasitas kontak: AC250V, 3A | S1~S4 | Lampu sinyal | Pangguna sing diwenehake |
| 10, 11 | Output antarmuka komunikasi, 10 yaiku (+), 11 yaiku (-) (Cathetan: Mode komunikasi Modbus-RTU standar) | TA | Transformator arus | |
| 12 nganti 15 | DO1, output sinyal sing bisa diprogram, kapasitas kontak: AC250V, 3A | SAL | Saklar Mikro | |
| 14, 15 | DO2DO3, output sinyal pambuka, kapasitas kontak: AC250V, 3A | SB1 | Tombol pambuka | Pangguna sing diwenehake |
| 16, 17 | DO4, output sinyal penutupan, kapasitas kontak: AC250V, 3A | SB2 | Tombol nutup | Pangguna sing diwenehake |
| 18.19 | Tanah (PE) | X | Elektromagnet sing nutup | |
| 20 | Pangukuran sinyal voltase, 21 disambungake menyang fase N, 22 disambungake menyang fase A, 23 disambungake menyang fase B, 24 disambungake menyang fase C | F | Pelepasan shunt | |
| 21, 22, 23, 24 | Input transformator N eksternal | Q | Pelepasan undervoltage | |
| 25, 26 | Pelepasan undervoltage | M | Mekanisme operasi listrik | |
| 27, 28 | Pelepasan shunt | SA | Saklar travel mekanisme operasi listrik | |
| 29.30 | Elektromagnet sing nutup | Fu | sekering | Pangguna sing diwenehake |
| 31, 32 | Mekanisme operasi listrik (panyimpenan energi listrik), 37 disambungake karo garis ijo, 38 disambungake karo garis ireng, 39 disambungake karo garis abang | PE | Kabel lemah | |
| 33, 34, 35 | Terminal kontak bantu | N | Netral (fase N) | |
| 36-48 | A, B, C | Garis fase | ||
| ★Amarga voltase sirkuit utama seri iki yaiku voltase dhuwur, pangukuran sinyal voltase saka kontroler tipe R/H 21,22/23,24 kudu disambungake menyang modul konversi voltase. | AX | Kontak bantu | Perakitan selektif | |
| Modul ST-DP | Parameter iki dibutuhake nalika mode komunikasi yaiku Profibus-DP | Perakitan selektif | ||
| Modul Daya ST | Fungsi komunikasi nalika dibutuhake | Perakitan selektif | ||
| Modul Relay ST201 | Fungsi komunikasi nalika dibutuhake | |||
Pemutus Sirkuit Universal Cerdas RDW8HU-2500 (Tipe Laci)
| Arus sing dirating (A) | Kekandelan busbar H(mm) |
| 630,800,1000,1250,1600 | 15 |
| 2000, 2500 | 20 |
RDW8HU-2500 Arus kasebut cocog karo kekandelan busbar
Pemutus Sirkuit Universal Cerdas RRDW8HU-2500 (dipasang)
| Arus sing dirating (A) | Kekandelan busbar H(mm) |
| 630,800,1000,1250,1600 | 15 |
| 2000, 2500 | 20 |
RDW8HU-2500 Arus kasebut cocog karo kekandelan busbar
Pemutus Sirkuit Universal Cerdas RDW8HU-4000 (Tipe Laci)
| Arus sing dirating (A) | Kekandelan busbar H(mm) |
| 800, 1000, 1250, 1600, 2000, 2500, 2900, 3200, 3600, 4000 | 20 |
Arus kasebut cocog karo kekandelan busbar
Pemutus Sirkuit Universal Cerdas RDW8HU-4000 (diperbaiki)
| Arus sing dirating (A) | Kekandelan busbar H(mm) |
| 800, 1000, 1250, 1600, 2000, 2500, 2900, 3200, 3600, 4000 | 20 |
Arus kasebut cocog karo kekandelan busbar
Pemutus Sirkuit Universal Cerdas RDW8HU-6300 (diperbaiki)
| Arus sing dirating (A) | Kekandelan busbar H(mm) |
| 4000 | 25 |
| 5000~6300 | 30 |
Pemutus Sirkuit Universal Cerdas RDW8HU-6300 (Tipe Laci)