1. Jinis piranti: jinis njaba ruangan
2. Suhu sekitar: suhu maksimal +40℃, suhu minimal -30℃
3. Dhuwur: 1000 meter (>1000 meter, kenaikan suhu kudu dikoreksi)
4. Suhu relatif: 90% (25 ℃)
5. Situs instalasi: ora ana gas korosif, ora ana rereget sing jelas lan area liyane
Transformator daya pengatur tegangan tanpa eksitasi tiga fase 110kV gulungan ganda
| Dirating kapasitas (kVA) | Kombinasi voltase lan rentang tap | Kopling klompok Label | Ora ana beban kerugian kW(9) | Mundhut beban kW(9) | Tanpa beban saiki% | Korsleting impedansi % | |
| Tegangan dhuwur (kV) | Endhek voltase (kV) | ||||||
| 6300 | 110±2×2.5% 115±2×2.5% 121±2×2.5% | 6.3 6.6 10.5 | YNd11 | 5.90 | 33.0 | 0.50 | 10.5 |
| 8000 | 7.10 | 40.0 | 0.50 | ||||
| 10000 | 8.40 | 48.0 | 0.46 | ||||
| 12500 | 9.90 | 56.0 | 0.46 | ||||
| 16000 | 12.0 | 69.0 | 0.43 | ||||
| 20000 | 14.1 | 84.0 | 0.43 | ||||
| 25000 | 16.6 | 99.0 | 0.40 | ||||
| 31500 | 19.7 | 117 | 0.38 | ||||
| 40000 | 23.5 | 141 | 0.36 | ||||
| 50000 | 28.2 | 166 | 0.34 | ||||
| 63000 | 33.3 | 198 | 0.30 | ||||
| 75000 | 13.8 15.75 18 21 | 37.8 | 224 | 0.26 | 12~14 | ||
| 90000 | 43.5 | 258 | 0.24 | ||||
| 120000 | 54.2 | 320 | 0.22 | ||||
| 150000 | 64.1 | 379 | 0.19 | ||||
| 180000 | 72.0 | 434 | 0.16 | ||||
Cathetan:
1. Posisi tunyuk -5% kanggo tunyuk arus maksimal.
2. kanggo transformator boost, luwih becik nggunakake struktur tanpa kran. Yen dibutuhake dening operasi, kran bisa disetel.
3. nalika tingkat beban rata-rata taunan transformator antara 45%-46%, nilai kerugian ing tabel bisa digunakake kanggo entuk efisiensi operasi paling dhuwur.
Transformator daya pengatur tegangan tanpa eksitasi telung fase 6300kVA-63000kVA
| Kapasitas sing dirating (kVA) | Kombinasi voltase lan rentang tap | Label grup kopling | Ora ana mundhut beban kW(9) | Mundhut beban kW(9) | Arus tanpa beban % | Impedansi sirkuit cendhak % | |
| Tegangan dhuwur (kV) | Tegangan rendah (kV) | ||||||
| 6300 | 110±2×2.5% 115±2×2.5% 121±2×2.5% | 6.36.610.5 | YNd11 | 5.90 | 33.0 | 0.50 | 10.5 |
| 8000 | 7.10 | 40.0 | 0.50 | ||||
| 10000 | 8.40 | 48.0 | 0.46 | ||||
| 12500 | 9.90 | 56.0 | 0.46 | ||||
| 16000 | 12.0 | 69.0 | 0.43 | ||||
| 20000 | 14.1 | 84.0 | 0.43 | ||||
| 25000 | 16.6 | 99.0 | 0.40 | ||||
| 31500 | 19.7 | 117 | 0.38 | ||||
| 40000 | 23.5 | 141 | 0.36 | ||||
| 50000 | 28.2 | 166 | 0.34 | ||||
| 63000 | 33.3 | 198 | 0.30 | ||||
| 75000 | 13.8 15.75 18 21 | 37.8 | 224 | 0.26 | 12~14 | ||
| 90000 | 43.5 | 258 | 0.24 | ||||
| 120000 | 54.2 | 320 | 0.22 | ||||
| 150000 | 64.1 | 379 | 0.19 | ||||
| 180000 | 72.0 | 434 | 0.16 | ||||
Transformator daya pengatur tegangan on-load tiga fase 6300kVA-63000kVA
| Kapasitas sing dirating (kVA) | Kombinasi voltase lan rentang tap | Kopling Label grup | Ora ana beban kerugian kW(9) | Mundhut beban kW(9) | Tanpa beban % saiki | Korsleting impedansi % | |
| HTegangan dhuwur (kV) | Tegangan rendah (kV) | ||||||
| 6300 | 110±8×1,25% | 6.3 6.6 10.5 21 | YNd11 | 6.4 | 33 | 0.51 | 10.5 |
| 8000 | 7.7 | 40 | 0.47 | 10.5 | |||
| 10000 | 9 | 48 | 0.47 | 10.5 | |||
| 12500 | 10.7 | 56 | 0.47 | 10.5 | |||
| 16000 | 12.9 | 69 | 0.44 | 10.5 | |||
| 20000 | 15.4 | 84 | 0.44 | 10.5 | |||
| 25000 | 18.2 | 99 | 0.41 | 10.5 | |||
Transformator Daya Pengaturan Tegangan On-Beban Tiga Fase Cerdas 110KV
| Kapasitas sing dirating (kVA) | Kombinasi voltase lan rentang tap | Kopling Label grup | Ora ana beban kerugian kW(9) | Muatan kerugian kW(9) | Tanpa beban % saiki | Korsleting impedansi % | |
| Tegangan dhuwur (kV) | Tegangan rendah (kV) | ||||||
| 31500 | 110±8×1,25% | 6.3 | YNd11 | 21.6 | 117 | 0.41 | 10.5 |
| 40000 | 6.6 | 25.8 | 148 | 0.37 | 10.5~18 | ||
| 50000 | 10.5 | 30.6 | 184 | 0.37 | |||
| 63000 | 21 | 36.3 | 220 | 0.34 | |||
Cathetan:
1. Transformator pengatur beban, sementara nyedhiyakake produk struktur buck.
2. Miturut kabutuhan pangguna, bisa nyedhiyakake produk kombinasi voltase liyane.
Posisi tap 3.-10% yaiku arus tap maksimal.
4. Nalika tingkat beban rata-rata taunan transformator antara 45%-50%, nilai kerugian ing tabel bisa digunakake kanggo entuk efisiensi operasi paling dhuwur.
Transformator Daya Pengatur Tegangan Tanpa Eksitasi Tiga Fase 110KV
| Kapasitas sing dirating (kVA) | Kombinasi voltase lan rentang tap | Grup kopling Label | Ora ana beban kerugian kW(9) | Mundhut beban kW(9) | Tanpa beban % saiki | Impedansi sirkuit cendhak % | ||
| Tegangan dhuwur (kV) | Tegangan Sedheng (kV) | Tegangan rendah (kV) | ||||||
| 6300 | 110±8×1,25% | 36 37 38.5 | 6.3 6.6 10.5 21 | YNin0d11 | 7.70 | 42.0 | 0.61 | Dhuwur-sedeng (10.5) Dhuwur-Endhek (18~19) Sedheng-endhek (6.5) |
| 8000 | 9.20 | 50.0 | 0.61 | |||||
| 10000 | 10.9 | 59.0 | 0.57 | |||||
| 12500 | 12.9 | 70.0 | 0.57 | |||||
| 16000 | 15.4 | 86.0 | 0.54 | |||||
| 20000 | 18.2 | 101 | 0.54 | |||||
| 25000 | 21.6 | 120 | 0.50 | |||||
| 31500 | 25.7 | 142 | 0.50 | |||||
| 40000 | 30.8 | 170 | 0.46 | |||||
| 50000 | 36.4 | 202 | 0.46 | |||||
| 63000 | 43.3 | 243 | 0.42 | |||||
Cathetan:
1. Transformator pengatur beban, sementara nyedhiyakake produk struktur buck.
2. Alokasi kapasitas gulungan tegangan dhuwur, sedheng, lan endhek yaiku (100/100/100)%.
3. Label grup sambungan bisa YNd11y10 yen dibutuhake.
4. Posisi tap -10% yaiku tap arus maksimum.
5. Miturut kabutuhan pangguna, voltase medium bisa dipilih supaya beda karo nilai voltase ing tabel utawa nyetel kran.
6. Nalika tingkat beban rata-rata taunan transformator udakara 47%, nilai kerugian ing tabel bisa digunakake kanggo entuk efisiensi operasi paling dhuwur.
Transformator Daya Pengaturan Tegangan On-Beban Tiga Fase Cerdas Kelas 110KV
6300kVA-63000kVA telung fase ganda-gulungan voltase rendah 35kV
| Dirating kapasitas (kVA) | Kombinasi voltase lan rentang tap | Kopling klompok Label | Ora ana beban kerugian kW(9) | Mundhut beban kW(9) | Tanpa beban % saiki | Korsleting impedansi % | |
| Tegangan dhuwur (kV) | Endhekvoltase (kV) | ||||||
| 6300 | 110±2×2.5% 115±2×2.5% 121±2×2.5% | 36 37 38.5 | YNd11 | 6.40 | 35.0 | 0.54 | 10.5 |
| 8000 | 7.70 | 42.0 | 0.54 | ||||
| 10000 | 9.0 | 49.0 | 0.50 | ||||
| 12500 | 10.5 | 59.0 | 0.50 | ||||
| 16000 | 12.5 | 72.0 | 0.46 | ||||
| 20000 | 14.8 | 89.0 | 0.46 | ||||
| 25000 | 17.5 | 105 | 0.42 | ||||
| 31500 | 20.7 | 126 | 0.42 | ||||
| 40000 | 24.6 | 147 | 0.39 | ||||
| 50000 | 29.5 | 183 | 0.39 | ||||
| 63000 | 34.9 | 220 | 0.36 | ||||
Cathetan:
Posisi tap 1.-10% yaiku tap arus maksimal
2. Kanggo transformator boost, luwih becik nggunakake struktur tanpa tap. Yen dibutuhake deningoperasi, kran bisa disetel.
3. Nalika beban rata-rata tahunan transformator antara 44%-47%, nilai kerugian ing tabel bisa digunakake kanggo entuk efisiensi operasi paling dhuwur.
Ringkesan Pungkasan:
1. Nilai kerugian tanpa beban ing kabeh tabel parameter ing ndhuwur minangka nilai parameter Standar Nasional Cina tipe 18. Perusahaan kita bisa nyetel miturut kabutuhan pangguna sing nyata.
2. Miturut kabutuhan pangguna, bisa ngasilake produk ing njaba kapasitas meja, parameter kinerjane gumantung saka kabutuhan.
3. Miturut lingkungan operasi sing beda-beda, kita bisa nyedhiyakake produk sing dirancang khusus.
4. Tegangan medium bisa dipilih supaya beda karo nilai tegangan ing tabel utawa kran, kran tekanan dhuwur kanggo milih kran pengaturan tegangan asimetris.
5. Impedansi sirkuit cendhak bisa dipilih beda karo nilai median tabel.
6. Ukuran pungkasan bakal tundhuk karo konfirmasi gambar sawise kontrak ditandatangani.
● Transformator daya pengatur tegangan beban ganda tiga fase 110kV
● Spesifikasi transformator daya sing beda-beda bisa dikembangake miturut kabutuhan khusus pangguna.